Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | Warranty Certificate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
I. System purpose :
Accurately and quickly detect the main insulation failure of power cables with voltage
levels of 35KV and below; calibrate the cable length; accurately detect the direction
and depth of the cable buried.
Product name | Model No. | Qty.(unit) |
cable fault pre locator | XHGG501B | 1 |
cable fault pinpointer | XHDD503 | 1 |
cable pipeline locator | XHGX504L | 1 |
high voltage pulse generator | XHHV535-4TS | 1 |
III. Main technical parameters of the system: :
1) Single chip controled computer, keyboard operation mode, strong anti-interference ability;
2)System functions: fault distance measurement, fault pinpoint location, propagation
speed test, cable path search, buried depth detection;
3)Test methods: low-voltage pulse, flashover method, audio method,
acousto-magnetic synchronization method, valley method, peak method,
electromagnetic induction method, etc.;
4)Test range: test distance: >30km, detection depth: 2-5m;
5)Measurement accuracy: Rough measurement error: ±10m (absolute value) or 1%
(relative value), fine measurement error: ±0.2m (fixed point, path, depth);
6)Sampling frequency: 200MHz, minimum resolution 0.5m (100m/us)
7)Sampling method: automatic continuous sampling, never miss any discharge
waveform.
8)Low voltage pulse: Width: Adaptive Amplitude: 400Vpp
9)Output power: path power: 100W
10)Shock high voltage: three voltage 8/16/32kV adjustable
11)Short circuit current:0~320mA
12)Burn through power:0~2048J