1). The apparatus can automatically identify breaker status of on or off for fracture and
operates accordingly with clue.
2). Independent fracture 12 can test and indicate connection status of fracture so that it is convenient for users to check wiring.
3). The device can store fifty sets of testing results.
4). Its big screen(320×240)LCD display is an advanced grey screen which does not
reflect or black screen in sunshine. Besides, its menu interface with clues of pictures and characters menu operation is rather personal and easy to operate.
5). The device has powerful graphical analysis function, which makes it possible to display waveform and measured data simultaneously. Thus testing process is more self-evident.
6). The device contains delay and protection function, which makes it possible to cutoff
coil voltage automatically after circuit breaker operates. Therefore, the circuit breaker and the testing instrument are well protected.
7). The device can be used to carry out electric and manual switch test.
8). The device can be used in experiment of low voltage and high voltage, and seek the
minimum voltage or closing voltage automatically.
9). It can be used in reclosing experiment for parameters measurement of closing-opening,
opening-closing and opening-closing-opening.
10). Parameter measurement of vacuum contactor (single coil) .
2. Technical Parameters
1). Time measurement: fracture 12
Inherent opening (closing) time
Different period of opening (closing)
Different period between opening (closing)
Bouncing time of closing (opening) (bouncing times)
Measurement range: 0.01ms~10000ms
Accuracy: 0.1%±2 characters
Speed measurement: opening(closing) speed
The average speed for designed period of time (distance or angle range)
Speed measurement range: 1mm sensor 0.01~25.00m/s,
0.1mm sensor 0.001~2.50m/s
360°angle sensor 0.01~25.00m/s
3. Distance measurement: moving contact travel ( travel)
Contact travel ( contact separation)
Overshooting travel or kickback (excess of stroke)
4. Sensor measurement range: linear displacement sensor 50mm, resolution: 0.1mm,
distance 0.1~50mm
linear displacement sensor 300mm, resolution: 0.1mm, distance 10 ~ 300mm(optional)
linear displacement sensor 500mm, resolution: 1mm, distance 10 ~ 500mm(optional)
5. Current measurement: 0 ~ 20A
reslution : 0.01A
the maximum value of
opening(closing) coil
6. Display screen: 320×240 Liquid Crystal Display, contrast adjustable
7. Data storage: 100 sets of measuring data
8. Printer: High speed thermal printer
9. Apparatus power supply: AC/DC 220V ± 10%;50Hz ± 2%
10. DC power supply: output voltage: 25 ~ 265V continuously adjustable, output
current:≤ 20A( short time)
11. Host volume: 360×250×140mm6
12. Operational environment: -10ºC~+50ºC
13. Relative humidity: ≤90%