Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
XHTX201D CT/PT ANALYZER is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, Degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopt LCD, self-equipped minitype printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
Major Test Functions and Technical Parameters
Function Table
I. Current Transformer (CT) | II. Voltage Transformer (PT) |
1. Magnetization Curve | 1. Excitation Characteristic Test |
2. Transformation Ratio Test | 2. Transformation Ratio Test |
3. Polarity | 3. Polarity |
4.5% and 10% error curve | 4. Withstand Test of Power Frequency Alternating Current |
5. Current Injecting | 5. Degauss |
6. Degauss | 6. Calculation of Knee Point Value |
7. Withstand Test of Power Frequency Alternating Current | 7. Actual Secondary Load Test |
8. Automatic Calculation of Excitation Knee Point Value | 8. Resistance Test |
9. Actual Secondary Load Test | |
10. Resistance Test |
Major Technical Parameters | |
Operational Power Supply: | AC220V±20V, 50~60Hz |
Equipment Power Supply Output Waveform: | Sine Wave |
Single Machine Output Voltage of Excitation Characteristic: | 0~2500V |
Excitation Output Current: | 0~20 A |
Single Machine Output Current of Transformation Ratio Test | 0~1000A |
CT ratio measurement range | 5~25000A/5A(5000A/1A) |
PT ratio measurement range | 1~500KV |
Load Range | 5~1000VA |
Resistance measurement range | 0.1~300Ω |
Error: | ≤0.5%(0.2%*Reading+0.3%*Range) |
Operating Temperature: | -10ºC~+40ºC |
Relative Humidity: | <90RH% |
Altitude | ≤1000m |
Overall Dimension(Length×Width×Height): | 400 *200 * 260(mm) |
Weight: | ≤23 Kg |