Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | 12 Months |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The XHSD183 Transformer tester automantic insulation oil flash point tester replaces the keyboard operation with an advanced touch screen. Which is used to test the opening and closing flash point values of petroleum products. Adopting foreign advanced technology, LCD large-screen Chinese/English display user interface, full-screen touch button prompt input, which is convenient and fast, open, fuzzy control integrated software, modular structure, meets the national standards, the United States, the European Union and other standards. It is an ideal replacement for imported instruments. Widely used in railway, aviation, electric power, petroleum industry and scientific research departments.
1. Adopting new high-speed digital signal processor, it makes the work more reliable and accurate;
2. One host can simultaneously control multiple test furnaces to test multiple samples, which is saving test time;
3. Detection, opening, ignition, alarm, cooling, printing, the entire experimental process is completed automatically;
4. Platinum heating wire, gas ignition mode;
5. Automatic detection of atmospheric pressure, automatically correct the test results;
6. Adopting the newly developed high-power high-frequency switching power supply heating technology, the heating efficiency is high, and the adaptive PID control algorithm is adopted to automatically adjust the heating curve;
7. If the temperature is over-value, then it automatically stops detecting and alarming;
8. Thermal micro-printer makes printing more beautiful and faster, which is with offline printing function;
9. Recorded history record with a time stamp, maximum to 255;
10. Perpetual calendar clock with temperature compensation, accurate time, automatically record the date and time of the measurement, and can run for more than 10 years in the state of power failure;
11. Adopt 320x240 large-screen graphic LCD display, Chinese/English user interface;
12. Full-screen touch screen button, which is intuitive and convenient to operate;
13. Built-in multiple execution standards, those are available.
1. Temperature measurement:
Range: room temperature - 400 ° C
Repeatability: 0.5%
Resolution: 0.1 °C
Accuracy: 0.5%
Temperature sensor: platinum resistance (PT100)
Flash fire sensor: ion detection ring
2. Ambient temperature: 10-40 ° C
Relative humidity: <85%
Supply voltage: AC220V ± 10%
Power: <500W
3. Heating rate: meet the national standards, the United States, the European Union and other standards.
4. Size:
Host: 190X260X285 (mm)
Heating furnace: 280X260X285 (mm)
5. Weight: 18kg
Welcome you contact us for more information