Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | Warranty Certificate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
XHDP series ultra low frequency high voltage generator
I. VLF HV Tester Series
IV.Technical parameters
1. Output voltage ratings: See Details of Table 1
2. Output frequency: 0.1Hz, 0.05Hz, 0.02Hz
3. Measurement accuracy: 3%
4. Positive and negative voltage peak errors: ≤ 3%
5. Voltage wave form distortion: ≤ 5%
6. Use condition: indoor and outdoor; temperature: -10ºC∽+40ºC
Humidity: ≤ 85%RH
7. Power: AC50Hz, 220V ±5%
8. Power supply fuse tube: See Details of Table1
Model no. | Rated Voltage | Load Carrying Capacity |
Power Fuse Tube |
XHDP-30 | 30kV (Peak) |
0.1Hz,≤1.1µF | 8A |
0.05Hz,≤2.2µF | |||
0.02Hz,≤5.5µF | |||
XHDP-40 | 40kV(Peak) | 0.1Hz,≤1.1µF | 8A |
0.05Hz,≤2.2µF | |||
0.02Hz,≤5.5µF | |||
XHDP-50 | 50kV (Peak) |
0.1Hz,≤1.1µF | 10A |
0.05Hz,≤2.2µF | |||
0.02Hz,≤5.5µF | |||
XHDP-60 | 60kV(Peak) | 0.1Hz,≤1.1µF | 10A |
0.05Hz,≤2.2µF | |||
0.02Hz,≤5.5µF | |||
XHDP-80 | 80kV (Peak) |
0.1Hz,≤1.1µF | 20A |
0.05Hz,≤2.2µF | |||
0.02Hz,≤5.5µF | |||
XHDP-90 | 90kV (Peak) |
0.1Hz,≤1.1µF | 30A |
0.05Hz,≤2.2µF | |||
0.02Hz,≤5.5µF |