Customization: | Available |
---|---|
After-sales Service: | After Sales Service |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The XHBX1501 transformer winding deformation tester (frequency response method) is used to test power transformers of 6KV and above and other special purpose transformers.
Scan mode:
1. Linear scanning distribution
Scanning measurement range: (10Hz) - (10MHz) 40000 scanning point, resolution 0.25kHz, 0.5kHz and 1kHz
2. Segment frequency scanning measurement distribution
Frequency scanning measurement range:
(0.5kHz)-(1MHz),2000scanning points;
(0.5kHz)-(10kHz)
(10kHz)-(100kHz)
(100kHz)-(500kHz)
(500kHz)-(1000kHz)
3.Other technical parameters:
Amplitude measurement range | (-120dB) to (+20 dB) |
Amplitude measurement accuracy | 0.1dB |
Scanning frequency accuracy | 0.01% |
Signal input impedance | 1MΩ |
Signal output impedance | 50Ω |
Signal output amplitude | ± 20V |
Test repetition percent | 99.9% |
Measuring instruments dimensions | (LxWxH) 300X340X120 (mm) |
Instrument's aluminum box size | (LxWxH) 310X400X330 (mm) |
Overall weight | 13kg |
Operating temperature | -10ºC to +40ºC |
Storage temperature | -20ºC to +70ºC |
Relative humidity | <90%, non-condensing |
Features of use
1. The transformer winding deformation tester consists of a measurement part and an analysis software part. The measurement part is controlled by a high-speed microcontroller and consists of signal generation and signal measurement. The measurement part is connected to a tablet computer through a wireless WIFI interface, which requires no wiring and is easy to use. Wireless Bluetooth and USB interfaces can also be used to connect to a tablet or laptop computer.
2. During the test process, only the connecting busbar of the transformer needs to be removed, and all tests can be completed without hanging the cover or disassembling the transformer.
3. The instrument has a variety of frequency linear sweep measurement system measurement functions. The linear sweep measurement scanning frequency is up to 10MHz. The frequency sweep interval can be divided into 0.25kHz, 0.5kHz and 1kHz, providing more analysis of the transformer deformation.
4. The instrument is highly intelligent, easy to use, and has multiple functions such as automatic range adjustment and automatic sampling frequency adjustment.
5. The software uses the windows platform and is compatible with Win98/2000/WinXP/Win7/Win8/Win10 systems. Provides users with a more convenient and easy-to-use display interface.
6. Provides comparative analysis of historical curves, can load multiple historical curves for observation at the same time, and can specifically select any curve for horizontal and vertical analysis. Equipped with an expert intelligent analysis and diagnosis system, it can automatically diagnose the status of the transformer winding, load 6 curves at the same time, automatically calculate the relevant parameters of each curve, automatically diagnose the deformation of the winding, and provide reference conclusions for diagnosis.
7. The software management function is powerful, fully considering the needs of on-site use, and automatically saving environmental condition parameters to provide a basis for diagnosing transformer winding deformation. The measurement data is automatically saved and has a color printing function to facilitate users to produce test reports.
8. The software has obvious humanization features. Most of the measured conditions are options. The detailed parameters of the transformer can be saved for diagnostic reference, and there is no need to input them on site. Information can be added and modified later, making it more convenient to use.
9. The software is highly intelligent. After the input and output signals are connected and the condition parameters are set, all measurement work can be completed, and historical waveform curves can be opened during measurement at any time for comparison and observation and to stop measurement.
10. The measurement time of each phase is less than 60 seconds, and the total time required for winding deformation measurement of a power transformer with high, medium or low windings (no limit on capacity and voltage level) is no more than 10 minutes.
11.When measuring the transformer, the wiring personnel can place the signal input and output leads arbitrarily without affecting the measurement results. The wiring personnel can stay on the transformer tank without coming down, which reduces labor intensity.
Packaging: Wooden case filled with foam
Shipping: by Air, Sea, Express, etc.
Shipping time: 7-15 days if it's in stock.
A: We are factory.
A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days if the goods are not in stock,
it is according to quantity.
A: Payment<=1000USD, 100% in advance.
If you have other questions, pls send us an inquiry below:
XI'AN XU&HUI ELECTROMECHANICAL TECHNOLOGY CO.,LTD
Building B8-01, Phase I, Ronghao Industrial City, No. 2098, Weiyang 9th Road, Gaoling District, Xi'an