Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
XZH TEST portable 0-35KV cable fault location system cable fault detector can accurately and quickly detect the main insulation failure of power cables with voltage levels of 35KV and below; calibrate the cable length.
The system include a ARC multi-shot cable fault pre locator, a three voltage high voltage surge generator.
Model number: XHGG502A, XHHV535-4TSC
XHGG502A | Cable fault pre-locator |
XHHV535-4TSC | 8/16/32kV high voltage surge generator |
The system can quickly detect low-resistance, short-circuit, open-circuit and disconnection faults of various types of power cables with different cross-sections and different media, high-frequency coaxial cables, local telephone cables, street lamp cables, and buried wires, as well as high-resistance leakage and high-resistance flashover for permanent main insulation faults ,calibrate the cable length.
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Sampling frequency | 1MHz~400MHz |
Low voltage pulse amplitude | 300V±15% |
Ranging range | ≥120km |
Test range | 100m/300m/500m/1km/3km/5km/10km/25km/50km/100km |
Pulse width | 0.15uS/0.30uS/0.60uS/1.20uS/2.4uS/5.0uS/7.5uS/10uS |
Minimum resolution | 0.07m |
Test blind area | ≤10m |
Measurement error | ≤±(0.5%×L+1m), L is the cable length |
Power supply mode | charging AC110V~240V, 50Hz/60Hz |
Pulse coupler withstand voltage | DC 35kV |
Volume and weight | L358mm×W284mm×H168mm-4.7kg |
Working conditions | Temperature -20ºC~+65ºC, relative humidity 90%, atmospheric pressure 750±30mmHg |
Name | Qty. |
Main unit | 1 |
Single Q line | 1 |
Double Q line | 1 |
Sampler | 1 |
Power cable | 1 |
Coupler high voltage cable A (optional) |
1 |
Ground wire (optional) |
1 |
Ground cable | 1 |
Impulse high voltage | 0~32kV, 0~16kV, 0~8kV three voltage gear adjustment |
High voltage accuracy | 2.5 level |
Built-in capacitor | 4μF/32kV,16μF/16kV,64μF/8kV Adjustable three-speed adjustment |
Built-in ARM filter | Coupler built inside, cooperate with TDR 502A, ARC test mode can be achieved. |
Discharge power | 0-2048J at each voltage level |
Impact power | 2KVA |
Burn current | 60m A @32kV, 120mA@16kV, 240mA@32kV |
Output voltage polarity | negative polarity |
Impact time | about 6-7 seconds for automatic impact, arbitrary control time for manual impact |
Indication | High-voltage side voltage metering, indication of output voltage and current in real time |
Over-current protection: | 9A (greater than 5S) low voltage side |
Operating mode | Single trigger, cycle, DC |
DC withstand voltage testing | Output voltage adjustment and indication range 0-32KV, Output current indication range 0-20A |
Safe protection | With zero start protection function, safe and reliable . Overvoltage, Over-current, Overheating protection. Automatic discharge after operation. |
Connecting cable(standard) | High voltage output cable: 5m, Protective earthing cable:5m, power cable: 3m.(If you need extension test cables, welcome you contact us for customization) |
Over temperature protection | 105ºC |
Volume(mm) | 740L×520W×880H |
Weight | not more than 130kg |
Power supply | AC220V±10%, 50Hz±2Hz |
Ambient temperature | -20~+50ºC |
Protection rating | Not lower than IP54 |
Certificate | CE ISO |
Packing list | |||
Name | Qty. | Name | Qty. |
Surge generator | 1 | Power cable | 1 |
HV output cable | 1 | Ground wire | 1 |
Discharge rod | 1 | Fuse | 5 |
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------