Technical specification
| Sampling frequency | 80MHz |
| Low voltage pulse amplitude | 100V±15% |
| Ranging range | ≥65km |
| Test range | 300m/1km/5km/25km/65km |
| Pulse width | 0.125uS/0.50uS/2.50uS/7.25uS/10.0uS |
| Minimum resolution | 0.1m |
| Test blind area | ≤20m |
| Measurement error | ≤±(0.5%×L+1m), L is the cable length |
| Power supply mode | charging AC110V~240V, 50Hz/60Hz |
| Volume and weight | L358mm×W284mm×H168mm-4.7kg |
| Working conditions | Temperature -20ºC~+65ºC, relative humidity 90%, atmospheric pressure 750±30mmHg |
Cable fault pre-location: with the reflectometer XHGG501A based on the low-voltage impulse reflection method(TDR), and high-voltage decay(flashover) method (DECAY), arc reflection method(single-shot).
The system has an automatic ranging function
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

The above photo shows cable fault distance measured by using high voltage flashover mode.
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------