Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | 12 Months |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
portable cable fault location testing set is designed for 35kV and below underground cable fault location.
Consist with TDR cable fault pre-locator(XHGG501D), cable fault pinpointer(XHDD503C), 0-35kV,2uF,1225J high voltage surge generator(XHHV535-2L)
Product name | Model | Function | Qty.(unit) |
cable fault pre locator | XHGG501D | for underground cable fault rough distance measurement,with low voltage pulse method and high voltage flashover method | 1 |
cable fault pinpointer | XHDD503C | Acoustic-magnetic synchronization method to accurately locate the fault point of the cable,with BNR and compass indication functions | 1 |
high voltage pulse generator | XHHV535-2L | surge discharging for underground cable fault locating & DC high voltage withstand voltage test equipment. | 1 |
1 | Filter parameters | All-pass: 100Hz~1600Hz. Low pass: 100Hz~300Hz. Qualcomm: 160Hz~1600Hz. Bandpass: 200Hz~600Hz. |
2 | Channel gain | 8 levels adjustable. |
3 | Magnetic channel gain | 8 levels adjustable. |
4 | Output gain | 16 levels (0~112db) |
5 | Output impedance | 350Ω |
6 | Acoustomagnetic positioning accuracy | less than 0.2m. |
7 | Path identification accuracy | less than 0.5m. |
8 | Power supply | 4*18650 standard lithium batteries. |
9 | Standby time | more than 8 hours. |
10 | Volume | 428L×350W×230H |
11 | Weight | 6.5kg. |
12 | Ambient temperature | -25~65ºC; Relative humidity: ≤90%. |
Cable fault pre-locator(XHGG501D)
High voltage surge generator XHHV535-2L
XHHV535-2L high voltage pulse generator is mainly used for impulse discharge during cable fault testing, and can also be used for DC withstand voltage testing of other electrical equipment.
This device integrates a DC high-voltage source, energy storage capacitor, discharge ball gap, etc. It is currently the lightest and most user-friendly portable DC impact high-voltage equipment. It is an ideal product for power cable fault detection.
Technical data
Impulse voltage | 0-32kV |
Precision of KV-meter | 1.5 |
Built-in capacitor | 2μF |
Discharge power | 0~1000J |
Output voltage polarity | negative polarity |
Over-current protection | 8mA (more than 3 seconds) |
Impact power | 400W |
Over temperature protection | 85ºC |
Volume(mm) | 540L×300W×450H |
Weight | no more than 25kg |
Working power supply | AC 220V±10%/50Hz±2Hz |
Ambient temperature | -20~+60ºC |