Mainly used for cable fault location, identification, path and depth of comprehensive testing.
Accurate location of ground low resistance faults and detection of faults or running cables.
Automatic impedance matching, multiple detection modes, suitable for all kinds of cable detection.
Multi-antenna, multi-channel, direct display of cable buried depth.
Technical Parameters:
Instrument features:
Performance
1.Receiver
Working frequency: low frequency (815Hz), intermediate frequency (8kHz), high frequency (33 kHz), radio frequency (83 kHz), 50Hz
Antenna mode: valley method (zero value mode), crest method (peak mode), step voltage method and clamp current method (A-frame)
Sound indication: FM tone that changes with signal strength
Current indication: display the effective current value of the cable under test (unit: mA)
Working temperature: -10ºC+55ºC
Battery model: 6 AA alkaline batteries
Power indicator: graphic display
Battery life: continuous work> 8 hours: intermittent work> 16 hours
Size: 70×20×11cm
Weight: 3kg (with battery)
Signal strength indication: ladder diagram, digital range 0-999
Gain control: manual adjustment, dynamic range of 100dB
Detection depth: the maximum detection depth is not less than 5 meters
Maximum detection distance: The cable with good insulation can be up to 15km in the direct connection method
Depth measurement: press the depth key to display three digits, the maximum depth can be measured up to 10 meters
Accuracy*: Low frequency: ±(1-5)%≤2.5m Radio frequency: ±(5-12)%≤2.5m
*Depending on the site environment, the shape of the non-concentric lines, the number of adjacent pipelines, and the return current of the soil
2.Transmitter
Working frequency: low frequency (815Hz), intermediate frequency (8kHz), high frequency (33 kHz), radio frequency (83 kHz)
Working mode: direct connection method, coupling method (caliper method), induction method
Matching load: 5 ohms-3000 ohms
Impedance display: five digits
Overheating and overcurrent: automatic protection
Power output: low gear, middle gear, high gear
Main Features:
1. Pinpoint buried cable fault; seeking the 50Hzcable path measurement;
2. with rechargeable batteries, no need electricity, easy to field operations;
3. Continuous automatic impedance matching, multiple detection modes, for a variety of complex pipeline detection;
4. Multi-antenna, multi-channel, direct display cable depth;
5. Current measurement for parallel pipelines; built-ohm meter to measure the loop resistance.
Packaging: Wooden case filled with foam
Shipping: by Air, Sea, Express, etc.
Shipping time: 7-15 days if it's in stock.
A: We are factory.
A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days if the goods are not in stock,
it is according to quantity.
A: Payment<=1000USD, 100% in advance.
If you have other questions, pls send us an inquiry below:
XI'AN XU&HUI ELECTROMECHANICAL TECHNOLOGY CO.,LTD
Building B8-01, Phase I, Ronghao Industrial City, No. 2098, Weiyang 9th Road, Gaoling District, Xi'an
Serena Lee