Customization: | Available |
---|---|
After-sales Service: | Warranty |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
XHHV535-2L+XHGG502+XHDD503D Portable Cable Fault Location system
Accurately and quickly detect the main insulation failure of power cables with voltage levels of 35KV and below; calibrate the cable length; accurately detect the direction and depth of the cable buried.
The portable cable fault location system is a 1-phase mobile cable test and fault location system made in a form trolley. It is designed for
Cable fault pre-locator | XHGG502: for cable fault distance test |
Cable fault pinpoint locator | XHHD503D: cable fault pinpointing, WITH path auxiliary viewing function |
High voltage surge generator | XHHV535-2L: To impact faulty cable to make it discharge |
Welcome you contact us for more information and service.
Cable fault pre-location: with the reflectometer XHGG502 based on the low-voltage impulse reflection method(TDR), and high-voltage decay(flashover) method (DECAY), arc reflection method(multi-shot).
XHGG502 cable fault pre-locator
Cable fault pre-location: with the reflectometer XHGG502 based on the low-voltage impulse reflection method(TDR), and high-voltage decay(flashover) method (DECAY), arc reflection method(single-shot/ multi-shot).
There are three test mode of XHGG502, low voltage pulse, high voltage flashover, ARC multi-shot.
--------------------------------------------------------------------------------------------------------------------------------------------------------
The below picture shows cable fault distance measured by using ARC multi-shot test mode of XHGG502.
--------------------------------------------------------------------------------------------------------------------------------------------------------
The below picture shows cable fault distance measured by using high voltage flashover test mode of XHGG502
--------------------------------------------------------------------------------------------------------------------------------------------------------
The below picture shows cable length or cable open circuit fault distance measured by using low voltage pulse test mode of XHGG502. When using the low voltage pulse method, it is not necessary to connect the high voltage pulse generator. Other test methods must be used in conjunction with a high-voltage pulse generator.
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
XHLJ504
The receiver combined with a headphone work together with a high voltage pulse generator can be used as a cable fault pinpointer
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
The XHHV535-2L high voltage pulse generator can be used impulse discharge and withstand voltage test in low and high voltage cable fault test. High-precision test cable fault sampling waveform module and small transformer are installed inside, which can truly achieve the effect of not being damaged by impact, and it also has the functions of automatic timing impact, manual impact and withstand voltage test.
This device integrates a high-voltage DC source, an energy storage capacitor, a discharge ball device, an automatic discharge device, and a voltage level switching device into a cart-type high-end experimental instrument. It is a trolley-type high-end experimental instrument. The equipment completely solves the problems of ease of use, portability, safety and reliability of traditional experimental devices.
When the XHHV535-2Ltrolley-type high-voltage pulse generator is in use, after selecting the function switch, press the start button to perform high-voltage boosting work. After use, press the stop button, and the internal system will automatically release the remaining high voltage on the accumulator.
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Application--Underground cable fault location
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Welcome you contact us for more professional service~