Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | Warranty Certificate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
I. System purpose :
Accurately and quickly detect the main insulation failure of power cables with voltage levels of 35KV and below; calibrate the cable length; accurately detect the direction and depth of the cable buried.
Product name | Model No. | Qty.(unit) | main function |
cable fault pre locator | XHGG502 | 1 | For underground cable fault rough distance measurement |
high voltage pulse generator | XHHV535-4TS | 1 | surge discharging for underground cable fault locating & DC high voltage withstand voltage test equipment |
III. Main technical parameters of the system: :
high voltage surge generator XHHV535-4TS | Surge voltage levels and adjustment ranges |
Level 1 : 0-8KV Level 2: 0-16KV Level 3: 0-32KV |
High voltage divider: | Voltage Accuracy 1.5 grade | |
Inside capacitor: | 4μF/32kV,16μF/16kV, 64μF/8kV | |
Surge energy: | 2048J | |
Surge power: | 2KVA | |
Operating mode | Single trigger/cycle/DC | |
Impact time | about 5 seconds for automatic impact, arbitrary control time for manual impact | |
Safe protection | With zero start protection function, safe and reliable | |
Discharge | Unique high-voltage measurement design, in the stop state, it will automatically discharge the internal capacitance of the device | |
DC withstand voltage testing | Output voltage adjustment and indication range 0-32KV, Output current indication range 0-20A |
|
Burn current | Up to 160mA | |
Connecting cable | High voltage output cable: 5m, Power supply cable: 1.8m, Protective earthing cable: 3m | |
Safety | Overvoltage, Over-current, Overheating protection. Automatic discharge after operation. |
|
Protection rating | Not lower than IP54 | |
GW | 120kg |