Customization: | Available |
---|---|
After-sales Service: | Warranty Certificate |
Warranty: | Warranty Certificate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
XHGG501A2 is designed for underground power cable fault per-locating, to provide quick accurate and safe measurement solution.
Measure the power cable of different sections, different media of various materials, short circuit, open circuit short line fault and the low and middle resistance fault.
1. Windows operating system, touch operation mode, wireless expert online guidance, scientific cable management, real-time report generation;
2. flashover wave superposition analysis; built-in operation instructions, cable data, measured cases, etc.;
3. With ranging, speed measurement, cable management and other functions;
4. 100MHz sampling frequency, minimum resolution 0.5m (100m/us)
5. Fully automatic continuous sampling, never miss any discharge waveform;
6. Test method: flashover method, low pressure pulse method, multiple waveform analysis method
Measuring method
|
TDR Measurement method flashover sampling and impulse current method
|
Pulse amplitude
|
100Vp-p
|
Pulse width
|
0.1uS/2uS
|
Output impedance
|
50
|
Resolution Ratio
|
0.5m
|
Dynamic range
|
>80db
|
Measuring distance
|
0-30km
|
Power supply
|
AC 220V+/-10% 50Hz DC 12 V / 10 Ah, continuous work for 4 hours |
Data storage
|
32GB for data.
|
Working conditions
|
temperature: -10 ºC ~ +45 ºC Relative humidity:90%
|
Dimensions
|
490mm*350mm*210mm
|
Weight
|
9.9kg
|