China Manufacturer Cable Outer Sheath Fault Location System

Product Details
Customization: Available
After-sales Service: Support
Warranty: 1 Year
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Manufacturer/Factory & Trading Company

360° Virtual Tour

Secured Trading Service
Diamond Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
5
Year of Establishment
2022-08-12
  • China Manufacturer Cable Outer Sheath Fault Location System
  • China Manufacturer Cable Outer Sheath Fault Location System
  • China Manufacturer Cable Outer Sheath Fault Location System
  • China Manufacturer Cable Outer Sheath Fault Location System
  • China Manufacturer Cable Outer Sheath Fault Location System
  • China Manufacturer Cable Outer Sheath Fault Location System
Find Similar Products
  • Overview
  • Product Description
  • Features
  • Product Parameters
  • Packing list
  • Company Profile
Overview

Basic Info.

Model NO.
XHHG520
Connectors
Coaxial BNC
Test Mode
Point Test
Usage
Digital Cable Tester
Test Region
Unformed
Cable Type
Shielded
Power
Electricity
Certification
CE
Customized
Customized
Color
Black
Transport Package
Wooden Case
Specification
62*39*75
Trademark
XZH TEST
Origin
Shaanxi

Packaging & Delivery

Package Size
62.00cm * 39.00cm * 75.00cm
Package Gross Weight
53.000kg

Product Description

Product Description
China Manufacturer Cable Outer Sheath Fault Location System
XHHG520 Integrated cable outer sheath fault tester i designed based on the MURRAY bridge principle. It can be used to locate the breakdown points of various wires and cables and the defect points with low insulation resistance but no breakdown.

The equipment uses an electric voltage regulator and an R-type transformer to form a high-voltage constant current source, and the voltage can be increased or decreased by key operation. The no-load voltage is 15kV, the short-circuit current is 100mA, and a high-sensitivity amplifier and a galvanometer are used to indicate the balance. A balanced bridge is formed with a proportional potentiometer, and the whole is placed at a high potential. The measuring cable is a specially designed double-core high-voltage rubber cable, and the four-terminal resistance measurement method is used to avoid the error introduced by the lead resistance.
It can quickly and accurately find hidden dangers such as grounding faults and excessive leakage current of the outer sheath of 10kV-500kV single-core and three-core high-voltage and extra-high-voltage cables.

At the same time, it can perform 5kV-15kV, 1-minute DC withstand voltage test on the outer sheath of high-density polyethylene and polyvinyl chloride cables. It is an essential special instrument for cable equipment maintenance of 10kv-500kV single-core and three-core high-voltage and extra-high-voltage cable operating units, extra-high-voltage cable engineering companies, and various power transmission and transformation engineering companies.
China Manufacturer Cable Outer Sheath Fault Location System
Features

Bridge part:
Output voltage is adjustable;
With high accuracy and stability;
Adopt high-sensitivity amplifier and galvanometer to indicate balance;
Zero protection;
Automatically test the fault point, but retain the manual test function;
Compared with the wave reflection method, the bridge balance method has no blind spot, which is used to judge the breakdown point of short cables and those close to the end.

Withstand voltage and positioning part:
With automatic protection functions for overcurrent, overvoltage and overheating;
With zero-position start protection, it is safer and more reliable;
Unique self-discharge design, as long as the high-voltage output is cut off, the high voltage itself is zero;
With current and voltage dual pointer meter display, intuitive and clear;
Positioning mode and withstand voltage mode can be switched with one button, which is convenient and fast;
There is no blind spot in the test range;
The receiver sensitivity is adjustable, which is more convenient for positioning;
Overcurrent protection switch function, withstand voltage mode and positioning mode are easy to use.

 The integrated cable outer sheath fault location system is particularly suitable for
1. High-resistance breakdown points of cables after laying, especially linear high-resistance breakdown points that are difficult to burn into low resistance, such as linear high-resistance breakdown of cable intermediate joints.
2. Flashover type breakdown points, after breakdown, the constant current source can maintain the arc, a stable current passes through the bridge, and the bridge has sufficient sensitivity.
3. Defect points that have not yet broken down but have low resistance, such as using a megohmmeter to find that the cable resistance is low, but the insulation defect point does not break down under the operating voltage.
Product Parameters

Bridge part:
1. No-load voltage ≥15kV;
2. Short-circuit current ≥100mA (when adjusting balance, it is recommended to set it at 5~40mA);
3. Positioning ratio accuracy ±(0.2%·L±1) meter;
4. Weight: 35kg;
5. Working power supply: AC 220V (±10%), 50Hz±1Hz; 8.4V built-in battery.
Voltage resistance and positioning part:
1 Input voltage: 220V (±10%), 50Hz (±2Hz);
2 Output voltage: 0~15kV (square wave) adjustable;
3 Output current: 0~200mA;
4 Output capacity: 2kVA;
5 Frequency adjustment: Min:0.2Hz, Max:5Hz (adjustable range).

Packing list
No. Name Quantity
1 Cable sheath fault tester 1
2 High voltage connecting wire 1
3 Power cord 1
4 Receiver 1
5 Fuse 5
6 High power jumper wire 1
7 Output wire (red, black) 2
8 Charger 1
9 Ground wire 1
10 Receiver clamp 1
11 A-frame ground rod + extended connecting rod 2
12 9V battery 1
China Manufacturer Cable Outer Sheath Fault Location System
China Manufacturer Cable Outer Sheath Fault Location System
Company Profile

China Manufacturer Cable Outer Sheath Fault Location SystemChina Manufacturer Cable Outer Sheath Fault Location SystemChina Manufacturer Cable Outer Sheath Fault Location SystemChina Manufacturer Cable Outer Sheath Fault Location SystemChina Manufacturer Cable Outer Sheath Fault Location SystemChina Manufacturer Cable Outer Sheath Fault Location System

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier